Issue:
Getting a input phase loss PHF fault on ATV12
Product Line:
Altivar Machine, ATV12
Environment:
All serial numbers
Cause:
• Drive incorrectly supplied or a fuse blown
• Failure of one phase
• 3-phase ATV12 used on a 1-phase line supply
• Unbalanced load
• This protection only operates with the drive on load
Resolution:
• Check the power connection and the fuses.
• Use a 3-phase line supply.
• Disable the fault by setting Input Phase loss detection IPL page 94 = nO.
• Check the motor connection and any isolating devices located between the drive and the motor (contactors, circuit breakers, etc.).
ATV12 user manual:
https://www.se.com/ww/en/download/document/BBV28581/
Getting a input phase loss PHF fault on ATV12
Product Line:
Altivar Machine, ATV12
Environment:
All serial numbers
Cause:
• Drive incorrectly supplied or a fuse blown
• Failure of one phase
• 3-phase ATV12 used on a 1-phase line supply
• Unbalanced load
• This protection only operates with the drive on load
Resolution:
• Check the power connection and the fuses.
• Use a 3-phase line supply.
• Disable the fault by setting Input Phase loss detection IPL page 94 = nO.
• Check the motor connection and any isolating devices located between the drive and the motor (contactors, circuit breakers, etc.).
ATV12 user manual:
https://www.se.com/ww/en/download/document/BBV28581/
Released for: Schneider Electric Philippines


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.