How do I reset the password on my KVM (AP5602, AP5610, AP5615, AP5616)?

Issue

Forgotten or lost password on my APC KVM Switch - models AP5602, AP5610, AP5615, or AP5616


Product Line
  • Rack Accessories - KVM Switches
    • AP5602
    • AP5610
    • AP5616


Enviromment
  • All serial numbers
  • All firmware versions


Cause

Lost or forgotten password


Resolution


By default, there isn't a password on the AP56XX series KVM Switches. If you need to reset the current password please follow these steps:
  1. Local access from the local OSD (on screen display) is required.
  2. Attempt to log in to the KVM. If AP5610, AP5615, or AP5616 an option for "forgot password" will be below the text field. Click this and go to the next step. If  you are using an AP5602, type "Admin" as the username (if necessary) and "help" as the password (both are case sensitive). Press enter and the KVM will display the screen in the next step.
  3. There will be a 16 digit key and EID number displayed. Alternatively, the EID number can be found on the sticker on the bottom of the KVM. Gather this information.  Do not navigate away from this screen.  The 16 digit key is a one time, unique key.
  4. Contact APC technical support (http://www.apc.com/support/contact/)
  5. The representative will be able to generate a backdoor password which will remove the password from the KVM when entered.

This password reset procedure only resets the local console password. If you have forgotten a username and password for WEB access, you will need to gain local console access and connect to the KVM with a serial connection in order to Restore the KVM to Factory Defaults via the console menu. After doing so, you will lose all of your settings but be able to login with the default WEB username and password of apc/apc.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings