How to configure the Network Management Card and PowerChute Agent to be discovered and managed by Solarwinds Orion Network Performance Management (NPM)
Issue:
How to configure the Network Management Card and PowerChute Agent to be discovered and managed by Solarwinds Orion Network Performance Management (NPM)

Product Line:
PowerChute Serial Shutdown
PowerChute Business Edition
Network Management Card

Environment:
Solarwinds Orion Network Performance Management (NPM)

Cause:
Informational

Solution:

Orion NPM is a network monitoring application. It delivers real-time views that enable you to track network performance visually. It ships with the APC PowerNet MIB preloaded. Some configuration is required on the APC Network Management Card (NMC) and PowerChute to manage them through SNMP with OrionNPM.

Network Management Card:

SMNPv1 Access is enabled by default - found in Administration-Network-SNMPv1-access. This allows the NMC to be discovered out of the box by NPM. To allow traps/alarms to be received by NPM, go to the NMC - Administration - Notification - SNMP Traps - Trap Receivers - Add Trap Receiver and add the IP address of the machine running NPM.

PowerChute Business Edition (PCBE):
PowerChute Serial Shutdown (PCSS):

PowerChute Business Edition version 9.5 & 10. offers SNMP v1 and SNMP v3 See the User's Guide attached.
"PowerChute Business Edition 10.0.5 -Type-A User's Guide." See pages 24 - 28

PowerChute Serial Shutdown: See the User's Guide attached.
"PowerChute Serial Shutdown Agent Type-A User Guide." See pages 25 - 29

NOTE:  PCBE version 9.2.1 and below only supports SNMP on Windows OS. The SNMP service (provided by Microsoft, seeFA159596 ) must be installed on the PCBE machine. In the PCBE Console, right-click the machine with the SNMP service installed, go to Properties - Communications - SNMP Communications, and tick the Enable SNMP Communications box (The 'Show Advanced Items' tickbox on the bottom of the window must be checked).

施耐德電機Taiwan

附件
PowerChute Business Edition 10.0.5 -TypeA User's Guide.pdf [1.34 MB]
PowerChute Serial Shutdown Agent Type-A User Guide.pdf [1.26 MB]
探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings