Why does PowerChute Network Shutdown not establish communications with Network Management Card when entering Radius user?
Issue:
PowerChute Network Shutdown will not establish communications with the Network Management Card when Radius is enabled.

Product Line/s:
PowerChute Network Shutdown
Network Management Cards (NMC) AP9630, AP9631, AP9635CH, AP9635, AP9640, AP9641

Environment:
All support OS

Cause:
PowerChute Network Shutdown does not support radius authentication.

Solution:
For AP9630, AP9631, and AP9635 running firmware 6.8 and above and all AP9640 and AP9641, you should enter a PowerChute user that will only be used by PCNS to communicate with the NMC. PCNS and the NMC will not utilize the Radius user. Go to Configuration—Shutdown and add the PowerChute user and authentication phrase.

PowerChute Shutdown Parameters for NMC firmware 6.8 and above

For AP9630, AP9631, and AP9635, running firmware 6.0 to 6.7.x PCNS and the NMC will not utilize the Radius user. Log into the NMC and verify the default apc user is enabled or create a new device or administrator user the PCNS and the NMC will use for communication. Then go to Configuration - Shutdown and select the PowerChute user from the username dropdown menu. The PowerChute username dropdown menu is populated with local users that have Administrative or Device user privileges.
PowerChute Shutdown Parameters for firmware older then 6.7.x

Note: AP9617, AP9618, AP9619 are no longer support.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings