我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
The simulator of Unity Pro V5 or V6.0 does not work when Windows Aero mode is activated! (August 2011)

Goals and Symptoms

On some PCs, the simulator of Unity Pro V5 or V6.0 doesn't run, because in the Appearance settings, Window Aero as Color scheme is selected.

Causes and Fixes

Replacing Windows Aero by Windows Basic (Standard or Classic) fixes this issue.
How to change the Color Scheme:
- Right-click on your desktop, then click Personalize. (Or, from the Start menu, select Control Panel and click Appearance and Personalization)
- Click Window Color and Appearance
- If Windows Aero is already selected, click Open classic appearance properties for more color options, then in Color scheme select Windows Basic, Standard or Classic

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings