Can a 0U PDU be hung upside down in the NetShelter SX cabinet?

Issue:
Installers may want to install a PDU in a manner that would be considered upside down.

Product Line:
NetShelter SX

Environment:
All versions and serial ranges.

Cause:
A customer may want to install the 0U PDU with the power supply cord facing either the top or bottom of the cabinet depending upon their preference, even if this causes the display to be upside down.

Resolution:

All APC by Schneider Electric brand 0U PDUs are designed to be installed into a NetShelter SX cabinet in either direction, with the supply cord facing up or down. The display can also be inverted to accommodate for the new orientation, please see the user manual for your device on how to do that.