What should I do when encountering an issue with the BR1100M2-LM, BR1350M2-LM and BR1500M2-LM
Issue:
Schneider Electric has recently identified a non-conforming level of internal operation involving several APC Back-UPS. This non-conformance is limited to the following SKUs;
  • BR1100M2-LM – Starting Serial Number 3B1937Xxxxxx
  • BR1350M2-LM – Starting Serial Number 3B1936Xxxxxx
  • BR1500M2-LM – Starting Serial Number 3B1939Xxxxxx

Product Line:
APC Back-UPS

Environment:

It has recently been discovered that the BR1100M2-LM, BR1350M2-LM, & BR1500M2-LM units, during installation and upon initial operation, may fail resulting in an F02/F04 error indicator present on the LCD display. In addition to the error indicator, the user may also observe light smoke and/or a flash of light internal to the UPS enclosure. The unit will remain in this fault condition, unable to be cleared.

Cause:
When the UPS is transferring to battery mode, in the first cycle of operation, insufficient circuit voltage may cause the FET to fail during the transition between states of operation.

Resolution:
The lower voltage of the gate driver has been corrected through a firmware design change implemented in our factories and all stock in Schneider Electric Inventory is currently undergoing this firmware design change as well.

We apologize for any and all inconvenience this may cause. Schneider Electric is continuously working to improve our products and to provide our customers with highest quality products possible.

Customers may contact their country specific Schneider Electric call center to process the necessary RMA exchange.

Distributors are asked to contact their Schneider Electric account sales manager for options to resolve this stocking issue.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings