PowerChute Network Shutdown Appliance: Events logged for host shutdown and maintenance mode are disappearing after PCNS restart

Issue:
Events logged for host shutdown and maintenance mode are disappearing after a PowerChute restart.

Products:
PowerChute Network Shutdown v4.3 and 4.4.2

Note: We recommend installing PowerChute version 4.4.3, configuring it, and then discontinuing the use of the older version. PowerShell and the PowerCLI have been preinstalled on PowerChute version 4.4.3, so when reviewing the script instruction, you can skip to the section to download settings.txt, disable_HA.ps1, and enable_HA.ps1 files.

Environment:
VMware vSphere 7U1 and above with vCenter Server 7U1 and above.

Cause:
Hard shutdown of PowerChute Network Shutdown Appliance when the host goes down.

Solution:
When the PowerChute Network Shutdown appliance is on the local datastore.


Enable automatic startup and shutdown for the PowerChute Network Shutdown appliance and set shutdown behavior to Guest Shutdown with a 120-second delay.

VM Startup Shutdown Image

When the PowerChute Network Shutdown appliance is on a shared datastore.

Configure PowerChute Network Shutdown with the attached scripts (enable_HA and disable_HA).  Please follow the instructions in the attached PDF (HA_ScriptInstructions).

NOTE: If vSphere Cluster Services (vCLS) is enabled on the cluster, the attached script will handle vCLS VMs as well.  For more information on using the script for vCLS, refer to KBase article FA416409.

施耐德電機Taiwan

附件
settings.txt [229 Bytes]
HA Scripts.zip [1.96 KB]
HA_ScriptInstructions.pdf [247.28 KB]
HA Scripts.zip [2.19 KB]
探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings