Q&A Zero set and Zero default for WAP10 IAN end node

Q: Can the WAP10 be calibrated in the field?

Answer: No, the absolute pressure transmitter cannot be calibrated in the field.

Q: Could you explain and double check the implementation of the zero set in the released IAN AP ENs?

Answer: The IAN Zero Offset operation is simplistic.  There are no protection mechanisms with respect to current reference value.  If user wants to apply zero offset for AP, a perfect vacuum would be the target pressure.

The IAN devices, including AP, do not support trimming operations.  There is no way to perform a “zero calibration”.  What the “Zero” operation does is perform a “Zero Offset” operation.

So, Yes, to perform a zero offset on an IAN AP device, the transmitter would need to be at full vacuum.


Q: What are the internal limits to the offset (zero set feature) for the WAP10? And, is the end node smart enough to know that the zero the user is trying to set is out of a limit imposed by the firmware?

Answer: The IAN devices have no limit checking when applying Zero Offset.

Q: If the WAP10 is not zeroed at full vacuum, the WiFi interface will not show any errors at all and it will just save the new zero whatever that value is. Correct?

Answer: YES.

Q: For a WAP10 if the user zeroed the meter at anything other than full vacuum, will the “Zero default” be able to recover the transmitter characterization and return the transmitter back to normal? Or would the user have to ship the unit back to be serviced in the factory?


Answer: The user can issue the “Zero default” at any time, to return unit back to normal.  No need to ship back to factory.


Q: How do you use the Zero Default? What process conditions does it need?

Answer: The AP transmitter can be cleared of the applied Offset, at any time, by reverting to the Zero “Default” via the WiFi overview page.

Zero Default button

The transmitter does NOT need to be at vacuum to “undo” (Default) the applied offset.  The Default can be applied at any pressure, to “undo” any currently applied offset.

Q: What would be the corrective action if the sensor has slightly drifted and the device indicates a value of 17 PSIA when exposed to an atmospheric pressure of 14.7 PSIA?
Answer: Due to the deviation of the reported pressure of 17 psia at 14.7 psia reference, we conclude that the instrument calibration is not functioning properly.

Because there is no way to remedy this in the field, the instrument should be returned to the factory for evaluation.

Questions: Help is available at FieldDevices-Support@se.com

施耐德電機Taiwan

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings