ETE - FAQ - Offer: How does EcoStruxure Transformer Expert work with DGA analysis?


For decades the transformer industry has used dissolved gas analysis (DGA) to assess the condition of transformers. Whenever a transformer undergoes abnormal thermal and electrical stresses, certain gases are produced due to the decomposition of the transformer oil. By observing the percentages of different gasses present in the oil, the internal condition of the transformer can be statistically assessed. Even though DGA provides evidence that there is something abnormal going on in the transformer, it has its limitations:

  • Specialized knowledge of standards such as IEC60599 and IEEE C57.104 are needed interpret the results.

  • DGA is a lagging indicator of the condition of the transformer i.e. DGA will only indicate major faults when the transformer has already started deteriorating to a critical point.

  • DGA cannot pinpoint the area in which the fault is occurring.

  • If the transformer has had an oil replacements, then the results won't reflect previous fault conditions.

  • Test results are highly influenced by the methods of extraction: time of day, temperature of the oil, location of the sample point, and the instruments used all impact the result.

  • Often absolute gas concentrations are insufficient to make any determinations about the health of a transformer. Instead, the historical rate of gas change over time is analyzed. For this to occur, DGA needs to be conducted routinely and under the same conditions to obtain comparable results. Accurate interpretation of these results also requires knowledge of the age of the unit, the loading cycle, and major maintenance such as filtering of the oil. It can be particularly difficult to maintain the required consistency when managing a fleet of transformers over the long lifetime of a transformer.

EcoStruxure Transformer Expert can help overcome some of these limitations:

  • Single web-based online platform to concurrently view online and offline data and manage transformer health over transformer life, across your fleet, whether that is just one or hundreds of transformers.

  • EcoStruxure Transformer Expert algorithms automatically analyse and interpret the DGA results according to the IEC standards and displayed in a graphical way so that trends are clearly identified. These can be understood by Asset Engineers and can remove the need for a specialized manager.

  • Concentration of gases and oil quality statistics can be compared over years through graphs, enabling the identification of escalating fault conditions.

  • Insights and Recommendations based on the DGA analysis are provided to each user, with configurable automated notifications of conditions of concern.

  • Health Indices clearly rank the transformers in the fleet for replacement and/or maintenance attention.

  • The analysis model combines online moisture, temperature, partial discharge and vibration data with DGA results to provide a comprehensive overview of transformer health. As offline data capture often does not capture the extremes of the transformer operating environment, the EcoStruxure Transformer Expert dashboard enables the user to see the impact of extreme conditions, overlaid with offline results on the same graph.  Together, the two sets of data provide a more complete picture of transformer health and its degradation over time. Insights and recommendations based on both sets of data are provided to users on how to operate a transformer to maximize efficiency and asset utilization.

  • The use of Furans from offline oil tests alone to determine the Degree of Polymerisation (DP) of the paper is notoriously inaccurate. The analysis uses these multiple sources of offline and online data to provide additional accuracy and Insights not available from standard DGA testing alone, including plotting the estimated aging profile of the paper insulation.

  • Multiple sources of data (DGA, oil test, loading cycle, sensor data) are correlated to increase reliability of results.


    See attached presentation at the bottom of this article to see some examples.

施耐德電機Taiwan

附件
FAQ000276011 - ETE & Oil Test Data V2.pdf [1.53 MB]
FAQ000276011 - ETE & DGA.pdf [1.83 MB]

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings