Issue:
Parameters to set up in a ATV320 Drive.
Product Line:
Altivar 320
Environment:
All ATV320 drives
Cause:
Basic programming
Resolution:
CONF>FULL>SIM
tFr= Max frequency
ItH= Motor thermal Current (motor FLA)
ACC= ramp up time
dEC= ramp down time
LSP= Low speed
HSP= High speed
CONF>FULL>drC
bFr= Base motor frequency 60hz
CONF>FULL>drC>ASY
nPr= HP of the motor
UnS= Rated motor voltage
nCr= Rated motor current (Motor FLA)
FrS= Rated motor frequency
nSP= Rated motor speed (RPM)
CONF>FULL>SET
CLI= current limit (maximum current, must be greater than FLA, up to 150% of FLA)
NOTE: Make sure to use the information on your motor's nameplate for programming.
Please refer to ATV320 Programming Manual, document # NVE41295 for additional details.
Parameters to set up in a ATV320 Drive.
Product Line:
Altivar 320
Environment:
All ATV320 drives
Cause:
Basic programming
Resolution:
CONF>FULL>SIM
tFr= Max frequency
ItH= Motor thermal Current (motor FLA)
ACC= ramp up time
dEC= ramp down time
LSP= Low speed
HSP= High speed
CONF>FULL>drC
bFr= Base motor frequency 60hz
CONF>FULL>drC>ASY
nPr= HP of the motor
UnS= Rated motor voltage
nCr= Rated motor current (Motor FLA)
FrS= Rated motor frequency
nSP= Rated motor speed (RPM)
CONF>FULL>SET
CLI= current limit (maximum current, must be greater than FLA, up to 150% of FLA)
NOTE: Make sure to use the information on your motor's nameplate for programming.
Please refer to ATV320 Programming Manual, document # NVE41295 for additional details.
Опубліковано для: Schneider Electric Україна


Потрібна допомога?
Інструмент вибору продукту
Швидко та легко знаходьте потрібні продукти й допоміжне обладнання для своїх завдань.
Розрахувати вартість
Ставте свої запитання щодо продажів онлайн, і з вами зв’яжеться фахівець
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Довідковий центр
Знайдіть усі необхідні ресурси для підтримки в одному місці.