Issue:
This video shows how to reset an Air Filter Run Hours violation alarm on a Uniflair Unit.
Product line:
All Unfair Units with Push-Button Display, All Chilled Water Uniflairs.
Environment:
All Serial Number with Push-Button Units.
Cause:
Repair, Install, Maintenance.
Resolution
To clear Air filters run hour violations from a Uniflair push button display.
Press <> PRG.
Settings Menu <> ENTER.
Code <> 00000 ENTER.
Hour-Meter Settings <> ENTER.
ENTER down to reset hit ENTER change display to OK and then ENTER Again.
Alarm has been cleared. Review the following video for a demonstration of this procedure.
This video shows how to reset an Air Filter Run Hours violation alarm on a Uniflair Unit.
Product line:
All Unfair Units with Push-Button Display, All Chilled Water Uniflairs.
Environment:
All Serial Number with Push-Button Units.
Cause:
Repair, Install, Maintenance.
Resolution
To clear Air filters run hour violations from a Uniflair push button display.
Press <> PRG.
Settings Menu <> ENTER.
Code <> 00000 ENTER.
Hour-Meter Settings <> ENTER.
ENTER down to reset hit ENTER change display to OK and then ENTER Again.
Alarm has been cleared. Review the following video for a demonstration of this procedure.
Опубліковано для: Schneider Electric Україна


Потрібна допомога?
Інструмент вибору продукту
Швидко та легко знаходьте потрібні продукти й допоміжне обладнання для своїх завдань.
Розрахувати вартість
Ставте свої запитання щодо продажів онлайн, і з вами зв’яжеться фахівець
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Довідковий центр
Знайдіть усі необхідні ресурси для підтримки в одному місці.