What are the replacement lugs for the LA, LH, and Q4 type circuit breakers?

Article available in these languages: Spanish

Product Line:
LA LH Q4 circuit breakers

Resolution:
The standard replacement lugs are catalog number AL400LA, which contains 1 lug per kit.
Several alternate lug kits are available, listed below:

Mechanical Lug Kit
Lug Kit Conductor
AL400LA AL400LAT(1) 1 AWG-600 kcmil AI/Cu (42-304 mm2)
(2) 1 AWG-250 kcmil AI/Cu (42-127 mm2)
CU400LA(1) 1 AWG-600 kcmil Cu (42-304 mm2)
(2) 1 AWG-250 kcmil Cu (42-127 mm2)
AL400LH7
AL400LH7T
(1) 1 350-750 kcmil AI/Cu (177-380 mm2)
AL250LAMC(1) 250-350 kcmil Al (42-304 mm2)
(1) 3/0 AWG-350 kcmil Cu (85-177 mm2)

"T" indicates control wire taps on the lugs.
See instruction bulletin, 48040-896-03

Compression Lugs
Lug KitConductor
VC400LA3(2) #4 AWG-300 kcmil AI/Cu (25-150 mm2)
VC400LA35(2) 250-350 kcmil AI/Cu (120-185 mm2)
VC400LA5(1) #2/0 AWG-500 kcmil AI/Cu (70-240 mm2)
VC400LA7(1) 500-750 kcmil AI (240-400 mm2)
(1) 500 kcmil Cu (240 mm2)
CVC400LA3(2) #2/0 AWG-300 kcmil AI/Cu (70-150 mm2)
CVC400LA5(1) 250-500 kcmil AI/Cu (120-240 mm2)

See instruction bulletin, 48040-699-03

Power Distribution Connectors
Lug KitConductor
PDC4LA250(3) 14-2 AWG Cu, (1) 2 AWG-250 kcmil Cu
PDC6LA20(6)12-2/0 AWG Cu
PDC12LA4(12) 14-4 AWG Cu

See instruction bulletin, 48040-929-04

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings