How many accessories can be installed in the PowerPacT M frame breaker?
Issue:
Can I install both a shunt trip and undervoltage relay in an M-frame breaker?
Product line:
Molded case circuit breakers
Resolution:
There are positions for up to three OF auxiliary switches, one SD alarm switch, and either a shunt trip MX or undervoltage MN. It does not have an option for the SDE overcurrent trip switch.
Can I install both a shunt trip and undervoltage relay in an M-frame breaker?
Product line:
Molded case circuit breakers
Resolution:
There are positions for up to three OF auxiliary switches, one SD alarm switch, and either a shunt trip MX or undervoltage MN. It does not have an option for the SDE overcurrent trip switch.
Released for: Schneider Electric USA