Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Are power factor correction capacitors recommended with Altivar Variable Frequency drives?
Issue:
Power Factor correction capacitors on the Altivar Variable Frequency Drives.

Product Line:
Altivar Drives

Environment:
All models and serial numbers

Cause:
None

Resolution:
Schneider Electric does not recommend using power factor correction capacitors with variable frequency drives.  Capacitor banks in distribution systems with 6 pulse variable frequency drives may result in undesirable resonant currents.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings