ION7x50 meter with EN50160 Frequency N,N1,N2 counts reset twice per year

Product Line
_____________________________________________________________
ION7650

Environment
_____________________________________________________________

ION Setup
PME Designer

Issue
_____________________________________________________________
When reviewing logged data for EN50160 Freq N, Freq N1, and Freq invld, the values will reset twice a year, First at the start of a new year then again at the start of some month.

Root Cause
_____________________________________________________________
Reset input to Signal limit Evaluation module 1 is pulsed twice in the same year. Logic in the framework is using double "not".

Solution
_____________________________________________________________
Change the Mode setup register of AND/OR module 11 "PQ Sync Yr Inv".
Default value is NOR, setting should be AND
Setup registers of AND/OR 11 module

Schneider Electric United Arab Emirates

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Change your cookie settings