What is the part number for a varistor coil surge suppressor for a LC1D09 to LC1D32 3 pole and LC1DT20 to LC1DT40 4 pole?

Issue:
Surge suppressor part number is needed

Product Line:
TeSys D line Contactors

Environment:
Products sold and used in the United States

Cause:
Need a varistor coil surge suppressor in their application

Resolution:
For 24 to 48 volts AC LAD4VE, for 50 to 127 volts AC LAD4VG, and for 110 to 250 volts AC LAD4VU.
These will limit the transient to 2 times nominal voltage and increases drop out time 1.1 to 1.5 times normal.