Can the ground fault feature on a Micrologic trip unit be defeated or turned off?
Issue:
Can the ground fault feature on a Micrologic trip unit be defeated or turned off?

Product Line:
Micrologic Trip Units

Resolution:
No. To use the breaker without ground fault, it is necessary to replace the trip unit with the appropriate LSI trip unit (or replace the breaker on breakers with non-interchangeable trip units).