How to configure the STBEHC3020 for event counting

Issue
How to configure the EHC3020 for event counting.

Product Line
All versions of the Advantys Configuration Software.

Environment
Windows 7

Resolution
Wire the 'EHC3020' to the incremental encoder.


  • Double click on the 'EHC3020' module to open the properties window for the module.
  • Configure the parameters as shown.
· Download the application to the island.

 
  • Start the PLC.
· Place the PLC into test mode.
  • Set the Input Validation bits to Off.
  • Set the Counter Enable to On.