What is the meaning of the B, C, D, K, and Z curves for C60 Multi-9 circuit breakers?
Issue:
What do the B curve, C curve, D curve, K curve and Z curve designations mean on Multi 9 breakers?
Product Line:
Circuit Breakers
Resolution:
For C60 Multi-9 devices, AC rated, the following is the meaning of the trip curves (in reference to instantaneous trip rating):
B curve: 3.2 - 4.8 times amp rating for UL489 and UL1077 (3 - 5 times amp rating for IEC)
C curve: 7 - 10 times amp rating
D curve: 10 - 14 times amp rating
K curve: 10 - 14 times amp rating
Z curve: 2.4 to 3.6 times amp rating
Released for: Schneider Electric Australia