Browse FAQs

ATV12 Can you have the run command from remote display and terminals?

Published date: 02 April 2020

Product Line:
All Altivar 12

Environment:
Any environment

Cause:
Run the drive from 2 command sources

Resolution:
Yes it is possible:
Navigate to ConF- /   FULL- /  CtL- /  FR1 = LCC
Then to CON- / FLO = L1H

This configuration will start the drive from the remote display (the green RUN button) and if we close the contact on LI1.


Was this helpful?

What can we do to improve the information ?