What resistor is required for the LX9FL replacement coils?
Issue:
What resistor is required for the LX9FL replacement coils?
Product Line:
TeSys F-Line Contactors
Environment:
All Product Lines
Cause:
Can not find it in the Digest
Resolution:
LX9FL918 48V coil uses resistor DR2SC0047
LX9FL925 110V coil uses resistor DR2SC0270
LX9FL926 125V coil uses resistor DR2SC0330
LX9FL931 220V coil uses resistor DR2SC1000
*The LX9FL937 coils are no longer available.
What resistor is required for the LX9FL replacement coils?
Product Line:
TeSys F-Line Contactors
Environment:
All Product Lines
Cause:
Can not find it in the Digest
Resolution:
LX9FL918 48V coil uses resistor DR2SC0047
LX9FL925 110V coil uses resistor DR2SC0270
LX9FL926 125V coil uses resistor DR2SC0330
LX9FL931 220V coil uses resistor DR2SC1000
*The LX9FL937 coils are no longer available.
Released for: Schneider Electric Australia