How can we help you today?
How does the ATV630 Process drives stall function work?
Issue:
How to set up stall function on the ATV630 Process drive?
Resolution:
- The output frequency is below the configured [Stall Frequency] (StP3).
- The output current is above the configured [Stall Current] (StP2).
- These conditions persist for longer than the configured [Stall Max Time] (StP1).
Example
Configuration:- StP3 (Stall Frequency) = 10 Hz
- StP2 (Stall Current) = 100% (motor rated current)
- StP1 (Stall Max Time) = 5 seconds
- If the drive operates at 9.9 Hz and the motor current exceeds the rated current, an StF (Motor Stall Error) is triggered after 5 seconds.
- If the drive operates at 10.1 Hz, the stall condition is not met and no StF error is triggered, even if the motor current exceeds the configured threshold.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric Australia
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.