How can we help you today?

ENM Monitoring and Diagnostics pages display "[Invalid Date]" for timestamps

Issue

The Event Notification Module (ENM) Monitoring and Diagnostics pages display [Invalid Date] in timestamp columns instead of the actual timestamp.

Product Line

ENM 8.3.x

Environment

PowerSCADA Expert 8.1

Power Monitoring Expert 8.1

Cause

Some Windows locales use special characters for AM/PM notation (e.g., Italian [Switzerland], Chinese [Singapore]). When Windows is configured to use one of these locales, ENM cannot properly format timestamps, resulting in [Invalid Date].

Resolution

Change the Windows locale to one that uses standard AM/PM characters.
Examples:

  • Italian (Italy)
  • Chinese (China)

Steps:

  1. Open Control Panel → Region and Language.
  2. Change the locale to a supported setting.
  3. Restart ENM services if necessary.

Notes

  • This issue applies only to ENM 8.x and PME 8.1.
  • Newer versions of PME and ENM have resolved this locale parsing issue.

Recommendation

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.comPME Version History

Schneider Electric Australia

Explore more

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.