{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Video: How to install a shunt trip or undervoltage trip on a PowerPacT B frame breaker

Issue:
How to install shunt trip or under voltage trip on a PowerPacT B-frame breaker

Product Line:
PowerPacT Molded Case Circuit Breakers

Resolution:
First, the breaker must be in the tripped position. Once in the tripped position, open the accessory cover and install the shunt or undervoltage in the left slot in the breaker. Push down until it clicks into place. When the cover is closed, the MN (undervoltage) or MX (shunt) green tab will be visible through the window. To remove the shunt or under voltage, take a thin object like a screwdriver, slide into the slot in the device, and push it up until it clicks out of place. For further instruction, see video below:

Schneider Electric Australia

Explore more
Explore more
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.