What is INFL error on Altivar process and how can it be eliminated?

Issue:
INFL Internal Real Time Clock Error

Product Line:
Altivar Process Drive

Environment:
ALL

Cause:
Wiring / Programming

Resolution:

INFL is a real time clock fault. This could be due to a communication error between the keypad and the drive. 
In order to reinitialize the communication:
  1. Power off the drive
  2. Remove the battery of the keypad
  3. Re-connect the keypad
  4. Power on the drive
If INFL is no longer displayed, power off the drive, insert the battery in the keypad and power on the drive.  If you reset the clock and again get INFL or error related to internal Real Time Clock, replace the battery.

 