Issue: ATV61 or ATV71 current flow that triggers an SCF3 Product Line: ATV61 / ATV71 series Environment: All models, All serial numbers Cause: Information not available in current literature. Resolution: SCF3 Principal : The purpose of this function is to detect a short circuit to the ground at the start-up or while running. Detection time: Quick hardware detection (a few μs) . Output current sum > 25% of the current rating of the drive.