{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
What ambient conditions are acceptable for operation and storage of the Masterpact NT and NW circuit breakers?
Issue:
What considerations must be made for ambient temperature, humidity, altitude, and vibration when storing or operating Masterpact NW and NT circuit breakers?

Product Line:
Circuit Breakers

Resolution:
Masterpact circuit breakers are suited for use:
At ambient temperatures between -13° F (-25° C) and 158° F (70° C). Operating the breaker above 104° F (40° C) may require derating or over bussing the circuit breaker. See the attachment for details.
At altitudes less than or equal to 13,000 ft. (3900 meters). At altitudes > 6600 ft. (2000 m), rerating factors apply.  See the attachment for details.
It is recommended that the equipment be cooled or heated to the proper operating temperature and kept free of excessive vibration and dust, and protected from water intrusion and condensation.
See the attachment for vibration, humidity, and storage recommendations.

Schneider Electric Australia

Attachment(s)
Operating Conditions for Masterpact NW and NT 0613CT0001.pdf [43.6 KB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: