En quoi pouvons-nous vous aider aujourd'hui ?

Does the ATS48 unit provide separate power terminals to connect cables that feed the line side of the shorting contactor?


Issue:
Does the ATS48 unit provide separate power terminals to connect cables that feed the line side of the shorting contactor?

Product Line:
Altistart 48

Environment:
All models and serial numbers

Cause:
All ATS48 Soft Starts

Resolution:
No.  None of the ATS48 units have separate terminals for the line side of the shorting contactor.  The ATS48 L1, L2, L3 terminals are for incoming line connections.  This may require that separate terminal blocks be used to connect the line side of the shorting (bypass) contactor.
Note:  There are contactor load terminals provided for A2, B2, C2.

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :

Besoin d'aide ?

Besoin d'aide ?

Sélectionnez le bon produit

Sélectionnez le bon produit

Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.

Obtenir un devis

Obtenir un devis

Effectuez une demande de renseignements en ligne et un expert vous contactera.

Où acheter ?

Où acheter ?

Trouvez facilement le distributeur Schneider Electric local le plus proche.

Centre d'aide

Centre d'aide

Trouvez des ressources de support pour tous vos besoins, en un seul endroit.

  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings