Can an I -Line breaker be converted to a Lug-in Lug-out breaker and vice versa? Can the I-Line shroud and connectors be replaced with lugs?

Article available in these languages: Espagnol

Issue:
Convert I-Line breaker to lugs on both ends breaker. Or lug-lug breaker be converted to an I-line breaker?

Product Line:
I-Line Panelboards, Molded Case Circuit breakers

Environment:
I-Line Breakers VS Unit Mount Breakers

Cause:
Product modifications

Resolution:
The I-Line connector cannot be removed or retrofitted in the field or by the factory.  A new circuit breaker must be ordered with the lug in/out terminations.
A unit mount breaker, with lug in and lug out cannot be converted to an I-line breaker.

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :

Besoin d'aide ?

  • Sélectionnez le bon produit

    Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.

  • Obtenir un devis

    Effectuez une demande de renseignements en ligne et un expert vous contactera.

  • Où acheter ?

    Trouvez facilement le distributeur Schneider Electric local le plus proche.

  • Centre d'aide

    Trouvez des ressources de support pour tous vos besoins, en un seul endroit.

  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings