What is an OLF fault on the ATS48?
OLF fault on the ATS48.
ATS48
All
None
OLF is a motor thermal fault.
1. Check programming of the Softstart
SEt menu
In – Motor FLA
ILt – Current limit (may increase to allow more current when starting)
ACC – Acceleration (depend on the torque control setting)
t90 – Initial starting torque (may not be visible, increase to increase the starting torque)
drC Menu
bSt – Voltage boost level (can be used to avoid any starting torque issues)
CLP – Torque control (turning CLP OFF will ramp according to ACC in the SEt menu)
2. Check wiring from soft start to motor and verify that terminal connections are properly torque
3. Check for blockage of the motor
4. Check for correct rotation of motor
5. Check that the motor and the soft start are sized correctly
6. Attempt to run motor and check the current draw on each phase of the output on the soft start.