What are possible causes of SCF1 motor short circuit faults on the ATV61 and ATV71?
SCF1 faults on the ATV61 and ATV71.
Product Line:
ATV71, Altivar 71
ATV61, Altivar 61
Environment:
All
Cause:
SCF1 [Motor short circuit] Short-circuit or grounding at drive output
Resolution:
- Check the cables connecting the drive to the motor, and the motor’s insulation
- Using a 1,000V Megger, test the motor and leads
- Check for tight wiring connections
- Perform the Transistor test via the [1.10 DIAGNOSTICS] menu with the motor connected.
- [Diagnostics] -> [Test Procedures] -> Transistor Test
- Run the drive open circuit (with the motor disconnected, OPL turned off, and Motor Control Type set to V/F 2pts) and check the drive's output (T) terminals for balanced voltages phase to phase
- [1.8 Fault Management] -> [Output Phase Loss] -> set to 'No'
- [1.4 Motor Control] -> [Motor control type] -> set to 'V/F 2pts'
- Perform a diode check using terminals U/T1, W/T2, V/T3, PA+ and PC-.
Next measure between PC- to T1,T2,T3 and then swap leads. (total of 12 measurements: 6 measurements to PA+ and 6 measurements to PC-)
-Values outside the acceptable range can indicate damage to the IGBT's or other components in the drive.
Return programming to original settings after testing is complete.
Publié pour: Schneider Electric Belgium




Besoin d'aide ?
Sélectionnez le bon produit
Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.
Obtenir un devis
Effectuez une demande de renseignements en ligne et un expert vous contactera.
Où acheter ?
Trouvez facilement le distributeur Schneider Electric local le plus proche.
Centre d'aide
Trouvez des ressources de support pour tous vos besoins, en un seul endroit.