Directional protection of 2 transformers in parallel: suggested alternative settings to avoid incorrect operation (i.e. spurious tripping) of Sepam units

Goals and Symptoms

Standard setting of angle for directional protection is in this case is 45° but incorrect operation ( (i.e. spurious tripping) can occur with this setting.

Facts and Changes

Key Words and Phrases:
unexpected trips, directional detection, undetected events, non-detection, unwarranted tripping

Causes and Fixes

Attached document explains which alternative settings can be used to avoid spurious tripping.

AEDL3


  • Last Revised: 13 June 2008 by DRM

    Applies To: Operation of Sepam Protection Relays

    Original Author: DM

    Public

    All content © 1992-2008 Schneider Electric


Legacy KB System (APS) Data: RESL191288 V2.0, Originally authored by KBAdPM on 02/27/2008, Last Edited by DaMi on 06/14/2008
Related ranges: Sepam series 80, Sepam series 40, Protection plan

Schneider Electric Belgium

Pièce(s) jointe(s)
FA179940_Spurious_Operation_of_the_Directional_Phase_Over-Current.pdf [26.97 KB]
En savoir plus
Gamme :
En savoir plus
Gamme :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings