How can the analog I/O be forced in a M340 application?

Use the IODDTs, T_ANA_IN_BMX for inputs and T_ANA_OUT_BMX for outputs in conjunction with the WRITE_CMD function block.
Once the WRITE_CMD function block in enabled, the two variable below of the IODDT, can be used to force the analog value. First assign the value (CMD_FORCING_VALUE) and then set the bit (FORCING_UNFORCING_ORDER). Reset the bit ((FORCING_UNFORCING_ORDER)) to unforce the analog channel.

Standard symbol Type Access Meaning Address
FORCING_UNFORCING_ORDER BOOL R/W Forcing/unforcing command. %MWr.m.c.4.13
CMD_FORCING_VALUE INT R/W Forcing value to be applied. %MWr.m.c.5

In order to force a channel, you have to use the WRITE_CMD (%MWr.m.c.5) instruction and set the %MWr.m.c.4.13 bit to 1.
To unforce a channel and use it normally, you have to set the %MWr.m.c.4.13 bit to 0.

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings