Up one level (back) button does not work in ION Enterprise Vista.

When drilling down to the next window the back button will always give the error message this is the top level diagram even though it isn't the top level this happens because the browse closes active window option is checked in Vista under the options menu. Uncheck this and the back button will work again.
If this is not an option or undesireable, this can be caused by the registry having the wrong path to the system folder. To resolve this do the following:

1) Open the registry by going to Start > Run > and type regedit > click ok
2) Navigate to the following directory where x.x is the version of ION Enterprise: HKEY_LOCAL_MACHINE\SOFTWARE\Schneider Electric\ION Enterprise\x.x
3) Find Root1 and verify that the path to the system folder is exactly what it should be.