How do you reset the fault over modbus on the ATS22 soft starter?

Issue:
Needs to reset the fault over modbus on the ATS22 soft starter.

Product Line:
Altistart ATS22

Environment:
All

Cause:
Fault reset over modbus

Resolution:
The CMD register is word 752.  If  you set bit 3 to a 1 on the CMD word  it will reset any resetable faults.

Schneider Electric Belgium

Pièce(s) jointe(s)
Modbus address words for the ATS22.pdf [332.67 KB]