Data Center Expert | Video: How do I configure StruxureWare to send e-mail notifications?
StruxureWare does not email when a device goes into alarm.
Product Line
StruxureWare Data Center Expert (DCE)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
- Virtual Appliance (AP94VMACT)
Environment
StruxureWare Data Center Expert (all versions)
StruxureWare Central (all versions)
InfraStruXure Central (all versions)
Cause
For StruxureWare Data Center Expert to email out when a device is in alarm the follow option must be configured.
The device (or manual threshold) must be associated to a Notification Policy
The Notification Policy must have an Action Associated
The Action must have the correct email address configured
StruxureWare must be able to reach the email server
Resolution:
The following will explain how to test and configure email notification within StruxureWare Data Center Expert.
Enter and Testing Email Settings
- Test email setting by going to the Systems drop down menu located at the top of the client
- Select Server Administration settings
- Select Email settings
- Enter then test displayed settings by using the Test Email Settings icon.
- Enter a valid email address
Creating and test email actions
- Click on Alarm Configuration drop down menu
- Select Manager Alarm Action
- Select Create (to test an action jump to Step 9)
- Select Send E-Mail then Next
- Enter an Action Name
- Click Add
- Enter email address then click OK (repeat steps 6 & 7 to add multiple emails
- Click Finish
- Test the action by selecting the action then click Test
Associating an Action to a policy
- Click on the Alarm Configuration Icon between Surveillance and Report
- Located at the bottom left corner right click on Default then select Edit (if missing go to the Windows drop down menu and select Restore Default Screen Layout)
- Locate and click the Add icon to the right side of the window
- Select the action to be associated to the Notification Policy
- Choose notification option
- Click OK
- Select Choose Thresholds to verify which Thresholds will be associated to this Policy
- Click on the Device Tab to verify which devices are associated to this Policy
- Click OK
*Note: By default all Devices are added to the Default notification policy.
Publié pour: Schneider Electric Belgium










Besoin d'aide ?
Sélectionnez le bon produit
Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.
Obtenir un devis
Effectuez une demande de renseignements en ligne et un expert vous contactera.
Où acheter ?
Trouvez facilement le distributeur Schneider Electric local le plus proche.
Centre d'aide
Trouvez des ressources de support pour tous vos besoins, en un seul endroit.