Issue:
Torque limitation and current limitation times adjustments
Product Line:
ATV71 ATV61
Environment:
All
Cause:
Need to delay current limit before the drive trips on fault.
Resolution:
Yes, the VFD can be configured for an action when status goes to CLI, current limitation, and after a time delay.
Goto menu 1.8 FAULT MANAGEMENT (FLt)
Goto submenu TORQUE OR I LIM. DETECT (tid-)
Select parameter Trq/I limit. stop (SSb) and set to the desired behavior in the event of switching to torque or current limitation.
Select parameter Trq/I limit. time out (Sto) and set the time delay for taking SSF "Limitation" fault into account.
Torque limitation and current limitation times adjustments
Product Line:
ATV71 ATV61
Environment:
All
Cause:
Need to delay current limit before the drive trips on fault.
Resolution:
Yes, the VFD can be configured for an action when status goes to CLI, current limitation, and after a time delay.
Goto menu 1.8 FAULT MANAGEMENT (FLt)
Goto submenu TORQUE OR I LIM. DETECT (tid-)
Select parameter Trq/I limit. stop (SSb) and set to the desired behavior in the event of switching to torque or current limitation.
Select parameter Trq/I limit. time out (Sto) and set the time delay for taking SSF "Limitation" fault into account.
Publié pour: Schneider Electric Belgium




Besoin d'aide ?
Sélectionnez le bon produit
Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.
Obtenir un devis
Effectuez une demande de renseignements en ligne et un expert vous contactera.
Où acheter ?
Trouvez facilement le distributeur Schneider Electric local le plus proche.
Centre d'aide
Trouvez des ressources de support pour tous vos besoins, en un seul endroit.