Power Monitoring Expert - I can't read an custom OPC tag that I exposed using OPC Server Assistant - error is 'ReadingIDUnknown'

Issue

When using OPC Server Assistant to expose custom tags for OPC; OpcTestClient  shows and error 'ReadingIDUnknown'

Product Line

Power Monitoring Expert 7.2.x

Power Monitoring Expert 8.x

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Environment

Using OPC Server Assistant with Power Monitoring Expert Software

Cause

This will happen if you rename a device after you have exposed the custom tag. This happens because the OPC Server Assistant uses the System Name when writing information to IONServicesConfiguration.xml, but the OPC Server looks for the Display Name when exposing the data. Once a device has been renamed, the System Name and the Display Name are no longer the same, thus the problem.

Resolution
To workaround this, it is necessary to manually edit the IONServicesConfiguration.xml file. You will need to remove the entry for your custom tag so that is is the section under the correct device name, i.e. the Display Name. Be sure to make a copy of this file before doing the manual edit in case an error is made.

As an example, here is a snippet of an example of IONServicesConfiguration.xml. In this case, a device was renamed from test.floor7650 to test.floor7650_MSB. Notice how the custom entry, that is bolded, added by the OPC Server Assistant used the original device name, i.e. the System Name:

<?xml version="1.0"?>
<i:IONServicesConfiguration xmlns="http://rddl.xmlinside.net/PowerMeasurement/configuration/IONServices/MeasurementTemplates/1/" xmlns:i="http://rddl.xmlinside.net/PowerMeasurement/configuration/IONServices/1/">
<i:ION>
<i:Src label="test.floor7650_MSB" name="test.floor7650_MSB">
<i:MTR ref="Full"/>
</i:Src>
<i:Src label="test.floor7650" name="test.floor7650">
<M label="IN47 Result" name="IN47 Result"/>
</i:Src>
</i:ION>

To correct this, the snippet above would be changed to the custom tag entry (i.e. the Display Name):

<?xml version="1.0"?>
<i:IONServicesConfiguration xmlns="http://rddl.xmlinside.net/PowerMeasurement/configuration/IONServices/MeasurementTemplates/1/" xmlns:i="http://rddl.xmlinside.net/PowerMeasurement/configuration/IONServices/1/">
<i:ION>
<i:Src label="test.floor7650_MSB" name="test.floor7650_MSB">
<i:MTR ref="Full"/>
<M label="IN47 Result" name="IN47 Result"/>
</i:Src>
</i:ION>

NOTE:  To run the OPC Test client you can refer to the following article: https://www.se.com/us/en/faqs/FA247061/

Schneider Electric Belgium

En savoir plus
Produit :
En savoir plus
Produit :

Besoin d'aide ?

Besoin d'aide ?

Sélectionnez le bon produit

Sélectionnez le bon produit

Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.

Obtenir un devis

Obtenir un devis

Effectuez une demande de renseignements en ligne et un expert vous contactera.

Où acheter ?

Où acheter ?

Trouvez facilement le distributeur Schneider Electric local le plus proche.

Centre d'aide

Centre d'aide

Trouvez des ressources de support pour tous vos besoins, en un seul endroit.

  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings