Issue:
Using an ATV12 drive on 230vac 1 phase input and getting 230vac 3 phase output.
Product Line:
Altivar 12
Environment:
All
Cause:
Needs to feed the drive 1 phase input and have 3 phase voltage coming out of the drive.
Resolution:
The ATV12 version with suffix M2 is designed for 230vac single phase input and will produce a 230vac 3 phase output.
The ATV12 version with suffix M3 is not designed or rated for single phase supply.
Note that all Altivar drives are designed to control / run 3phase motors. They are not designed for phase converter applications to power a machine that includes various loads such as contactors, transformers, relays, heaters, pilot lights etc...
Using an ATV12 drive on 230vac 1 phase input and getting 230vac 3 phase output.
Product Line:
Altivar 12
Environment:
All
Cause:
Needs to feed the drive 1 phase input and have 3 phase voltage coming out of the drive.
Resolution:
The ATV12 version with suffix M2 is designed for 230vac single phase input and will produce a 230vac 3 phase output.
The ATV12 version with suffix M3 is not designed or rated for single phase supply.
Note that all Altivar drives are designed to control / run 3phase motors. They are not designed for phase converter applications to power a machine that includes various loads such as contactors, transformers, relays, heaters, pilot lights etc...
Publié pour: Schneider Electric Belgium
Besoin d'aide ?
Sélectionnez le bon produit
Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.
Obtenir un devis
Effectuez une demande de renseignements en ligne et un expert vous contactera.
Où acheter ?
Trouvez facilement le distributeur Schneider Electric local le plus proche.
Centre d'aide
Trouvez des ressources de support pour tous vos besoins, en un seul endroit.