En quoi pouvons-nous vous aider aujourd'hui ?
How to quickly determine what measurements have been logged for a source in PME
Product Line:
StruxureWare Power Monitoring 7.0.x
Power Monitoring Expert 7.2.x / 8.x / 9.0 / 2020 / 2021 / 2022 / 2023

Environment:
SQL Server Management Studio

Resolution:

*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*

1) The following query can be run in SQL Server Management Studio. It will return a list of all measurements that have been logged (at least once) for the given source, as well as the Min and Max timestamps of the data in the ION_Data database.

USE ION_Data
Select * From dbo.vSourceQuantityName
Where SourceName = 'Group.Meter'
Order by QuantityName

Replace 'Group.Meter' with the name of the source you are trying to query (leave the single quotes).

*Note: The above query will work in Power Monitoring Expert 9.0 and up, however the new Manual Data Editor can also be used to quickly determine what measurements have data for a particular source.

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings