SFT2841 - why do I receive an "Error: 1004" message when trying to load a settings file into my relay?
Based on reports from the field and internal investigations, this error typically appears during the loading of a settings file. We have seen this error on Series 40 and Series 80 relays primarily, although it could theoretically occur with Series 20 relays also.
This appears to be a timeout error between the SFT2841 software and the low-level communication drivers of the host PC's operating system. The following factors may contribute to this issue:
1) using an older computer with insufficient RAM or a relatively slow CPU to run Windows 7 (whereas the PC was originally intended to run Windows XP, for example)
2) using a 3rd-party (non-Schneider) USB to RS-232 converter to connect to a Sepam with the older "mini-DIN" round port
3) slow USB communication driver performance
Generally speaking, this is not a serious error, and usually the best solution is to simply retry the loading of the settings file. A failed settings file loading operation should not cause any permanent damage to the relay. If the error persists, you may wish to install the SFT2841 software on a faster computer, and also to use a Schneider-brand (e.g., Telemecanique TSXUSB) converter to connect to your Sepam (if applicable).
Please contact Technical Support if you have tried these resolutions but the error still persists.
AEDL3
Publié pour: Schneider Electric Belgium
Besoin d'aide ?
Sélectionnez le bon produit
Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.
Obtenir un devis
Effectuez une demande de renseignements en ligne et un expert vous contactera.
Où acheter ?
Trouvez facilement le distributeur Schneider Electric local le plus proche.
Centre d'aide
Trouvez des ressources de support pour tous vos besoins, en un seul endroit.