En quoi pouvons-nous vous aider aujourd'hui ?

How do you set up the damper control on the enclosed S-Flex ATV212 Drive?

Wants to wire in a damper control circuit to allow the damper to open before running the motor thru the drive.

Step #1 Customer commands the drive to run by closing terminals (5-6) auto start. (Drive will not start at this time or until damper is opened)

Step #2 Closing the auto start terminals  (5-6) will energize the RPR relay which will close user contacts (19-20) to start damper solenoid coil.

Step #3 Damper solenoid will start to open damper.

Step# 4 Once the damper is open the customer will need to provide a end of damper feedback limit switch.

Step #5 Remove the jumper from terminals (3-4) and wire your end of damper feedback dry NO contact to terminal (3-4).

Please note that this damper function will only work in the remote control mode by closing contacts (5-6) and not the local mode run button on the face of the drive.

Schneider Electric Belgium

Pièce(s) jointe(s)
Damper Control.jpg [97.61 KB]
En savoir plus
Produit :
Gamme :
En savoir plus
Produit :
Gamme :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings