What are the current threshold limit values for ‘0-20mAmp’ and ‘4-20mAmp’ current modes within the TM3AI8x analog input module ?
When the input read value is outside the limited range of value , the diagnostic information becomes as “ value out of range” , then the PLC application have to care about the diagnostic , but not to the provided value %IWi.x (which is no more the real one seen by the TM3 module, but a truncated value equal to the limit value)
The below table gives the limit range values which involve the channel diagnostic being as “limit exceed” (value 5 for low limit and 6 for high limit), according the different configuration modes available for current measurement within the TM3AI8 module
| Configuration mode | Low limit value | High limit value |
| 0-20mAmp | -0.4 mAmp | 20.4 mAmp |
| 4-20mAmp | 3.68 mAmp | 20.32 mAmp |
| 0-20mAmp Extended | -0.4 mAmp | 23.54 mAmp |
| 4-20mAmp Extended | 1.20 mAmp | 23.17 mAmp |
We can see the limit is always different , whatever is the selected mode
Note: for other analog input modules managing current mode: TM3AI2, TM3AI4, TM3AM6 , TM3TI4, TM3TM3, they have same limit values ,as shown into the table above, for 0-20mAmp and 4-20mAmp and they do not support the two “extended” modes.