How to understand the connection and device number of NOC
Answer to this question:
128 devices and 256 connections are not conflicted.
128 devices: Means the NOC module as Client for Implicit communication (IO scanning), so the TesysT configured by IO scanning, the maximum connections configured in IO scanning is 128. e.g. 128 TesysT devices, one IO scanning for one device; If 64 TesysT devices, two IO scanning for one device. 64x2=128.
256 connections of NOC, including EIP and ModbusTCP, Client and Server, FTP connections, Http connection.... 256=128(EIP share with ModbusTCP IO scanner) + 3x2 (EIP adapter)+16 (EIP explicit client)+32(EIP explicit server)+16(ModbusTCP explicit client)+32(ModbusTCP explicit server)+ some FTP and http.