Why does the ATV630 drive not save parameters when programmed over Modbus RTU?
ATV630 drive does not save parameters when programmed over Modbus RTU.
Product Line:
Altivar 630, Process
Environment:
All
Cause:
N/A
Resolution:
Modbus register value 8504 (CMI) will need to be written to in order for the drive parameters to be saved over the network.
CMI
Bit 0: Factory setting command (active at 1).
Bit 1: Save configuration to EEPROM non-volatile memory command (active at 1).
This Bit automatically changes to 0 after the request is taken into account. The command is only active if the drive is stopped, and not in "5-Operation enabled" state.
Bit 2: Reserved (= 0).
Bit 3: Reserved (= 0).
Bit 4: Reserved (= 0).
Bit 5: Reserved (= 0).
Bit 6: Reserved (= 0).
Bit 7: Reserved (= 0).
Bit 8: Reserved (= 0).
Bit 9: Definition of the frequency reference (LFr) and output frequency (rFr) unit:
= 0: 0.1 Hz
Bit 10: Reserved (= 0).
Bit 11: Reserved (= 0).
Bit 12: Reserved (= 0).
Bit 13: Reserved (= 0).
Bit 14: Reserved (= 0).
Bit 15: Parameter consistency check