Uniy Pro V11, Local Init value not updated with PLC init value

In Unity Pro V10 and previous, a Build is mandatory after command "Update Local Init values with PLC Init values".

But in Unity Pro V11 it is not always required to Rebuild application after command "Update Local Init values with PLC Init values".
Consequently, the init value are not correctly updated in the local application, although they seems correct in the Data Editor (colum "value").
So, if application is transfered from computer to PLC, the init value will not be the ones expected (values displayed in Data Editor).

Unity Pro V11.1 will fix this issue : a Build will be mandatory after command "Update Local Init values with PLC Init values".

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :

Besoin d'aide ?

Besoin d'aide ?

Sélectionnez le bon produit

Sélectionnez le bon produit

Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.

Obtenir un devis

Obtenir un devis

Effectuez une demande de renseignements en ligne et un expert vous contactera.

Où acheter ?

Où acheter ?

Trouvez facilement le distributeur Schneider Electric local le plus proche.

Centre d'aide

Centre d'aide

Trouvez des ressources de support pour tous vos besoins, en un seul endroit.

  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings