Issue:
The ATV630 drive is surging the motor when the drive is running in auto mode.
Product Line:
ATV630
Environment:
All
Cause:
Analog input was getting interference noise and analog input was oscillation up and down.
Resolution:
Check to see if you're experiencing noise on his line causing motor/drive fluctuations. If so, activate the applicable analog input filter (AI1F or AI2F). Set to 5 seconds.
The ATV630 drive is surging the motor when the drive is running in auto mode.
Product Line:
ATV630
Environment:
All
Cause:
Analog input was getting interference noise and analog input was oscillation up and down.
Resolution:
Check to see if you're experiencing noise on his line causing motor/drive fluctuations. If so, activate the applicable analog input filter (AI1F or AI2F). Set to 5 seconds.