Issue:
ATV930 process drive causes to get a precharge capacitor fault.
Product Line:
ATV930 process drives
Environment:
All
Cause:
DC bus tie with another drive
Resolution:
In a configuration where the drive is connected and supplied by another drive via the DC bus, set DCBS parameter (Generic Functions/DC-Bus Ref Link) to "Drive with REC" as shown in the attachment. This will avoid "Precharge Capacitor" faults due to power supplied direct to the DC bus.
[Complete settings] -> [Generic functions] -> [dbS] -> [dCbS] -> [Drive with REC]
More details can be found on page 441 of the ATV900 Programming Manual:
https://www.se.com/ww/en/download/document/NHA80757/
Note: the ATV600 series is not designed for applications where the DC bus is powered from an external DC source.
ATV930 process drive causes to get a precharge capacitor fault.
Product Line:
ATV930 process drives
Environment:
All
Cause:
DC bus tie with another drive
Resolution:
In a configuration where the drive is connected and supplied by another drive via the DC bus, set DCBS parameter (Generic Functions/DC-Bus Ref Link) to "Drive with REC" as shown in the attachment. This will avoid "Precharge Capacitor" faults due to power supplied direct to the DC bus.
[Complete settings] -> [Generic functions] -> [dbS] -> [dCbS] -> [Drive with REC]
More details can be found on page 441 of the ATV900 Programming Manual:
https://www.se.com/ww/en/download/document/NHA80757/
Note: the ATV600 series is not designed for applications where the DC bus is powered from an external DC source.
Publié pour: Schneider Electric Belgium
Besoin d'aide ?
Sélectionnez le bon produit
Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.
Obtenir un devis
Effectuez une demande de renseignements en ligne et un expert vous contactera.
Où acheter ?
Trouvez facilement le distributeur Schneider Electric local le plus proche.
Centre d'aide
Trouvez des ressources de support pour tous vos besoins, en un seul endroit.