YES, the product can function correctly.
Below is the front panel setting and waveform diagram.
Ti = Starting inhibit time delay adjustment potentiometer.
Function: On energisation, an inhibit time delay (1…20 s) makes it possible to inhibit (or ignore) current peaks on start-up of equipment.
You can try to adjust the RM35JA32MW product’s Ti setting to inhibit the inrush current during load start-up.
Below is the front panel setting and waveform diagram.
Ti = Starting inhibit time delay adjustment potentiometer.
Function: On energisation, an inhibit time delay (1…20 s) makes it possible to inhibit (or ignore) current peaks on start-up of equipment.
You can try to adjust the RM35JA32MW product’s Ti setting to inhibit the inrush current during load start-up.